FEATURES

  • IntelliLogger is a 16/32 Channel Modbus ID Monitoring System for Transmitters are having RS - 485 Modbus RTU Network Connectivity.

  • IntelliLogger has one more RS - 485 Modbus RTU Port for Remote Repeater Panel called as IntelliRepeater which will repeat all readings & Alarm conditions.

  • Multidrop RS - 485 Port eliminates separate cabling to each Transmitter and Monitor Panel.

  • Modbus - RTU Network can be connected in Ring Topology for Redendency.

  • Scan time for 16 Transmitter < 5 sec. & for 32 Transmitter < 10 sec.

  • Large 16 x 4 line Display with Configurable Backlit Option.

  • Auto Page Changing Facility available for easy viewing of Data, Relay & Fault Condition of each Transmitter.

  • Optional 8 Relays (SPDT) rated "10A / 250VAC, 10A / 30VDC" as Warning / Trip Relay with 1 no.  Failsafe Relay which activates for UNDER / OVER / OPEN Condition of Transmitter.

  • Separate Alarm Setting for each Transmitter with Logic High / Low & Latching Facility.

  • Password Protected Menu with Password Changing Facility.

  • Easy Handling & Programming with 3 keys on Front Panel.

  • Data Logging Capacity upto Six Lakhs Readings for 16 / 32 Transmitter.

APPLICATIONS

  • Clean Room Monitoring & Validation in Pharmaceutical, Laboratories, Bioscience

  • Room Mapping in Pharmaceutical

  • Pharmaceutical process validation with graph & scale report in Autoclave

  • Healthcare, Hospitals, Shopping Malls

  • Breweries, Steel Plants, Gas Turbines,

  • Leak detection, Solvent Vapors,

  • Personal Monitoring, Compressor Stations,

  • Emergency response, Equipment Maintenance

  • Pulp & Paper Industry, Fuel Loading Facilities

  • Waste Water Treatment Plants,

  • LNG / LPG Processing & Storage Facilities

  • Refineries & Petrochemical Plants Including Offshore

  • Drilling & Plant Shut-downs

  • ISO Certification Records, Validation process certifying,

  • Chemical & Hazardous area where data monitoring is essential

  • Food Processing

  • Cold Storage & Chilling Plant

  • Building Management & Energy Saving Systems

  • Meteorological, Weather Forecast Applications

  • Remote Indication location on tank taps as used in liquid level sensing &  control

General

  • Input: 16/32 Transmitters having RS-485 Modbus RTU Port.

  • Display

    • 16 x 4 Alphanumeric LCD with Configurable Backlit option.

    • 8 LEDs to indicate status of IntelliLogger.

    • 48 LEDs to indicate Alarm status of Transmitters in Group Function.

  • Control Action

    • 2 independent Alarm set points for each Transmitter with Latch & Non-Latch Facility.

    • User selectable Hysteresis & Logic Operation.

  • Setting: By using 3 keys on the front panel for WP & FLP models.

  • Log Capacity: Upto Six Lakhs Readings for 16 / 32 Transmitters.

Performance

Scan Time

  • Less than 5 Sec. for 16 Transmitters having RS-485   Modbus RTU Port.

  • Less than 10 Sec. for 32 Transmitters having RS-485 Modbus RTU Port.

Electrical

  • Supply Voltage: 190 to 270 VAC; + 20%, 50Hz.

  • Power Rating: Approx 20W.

  • Transmitter: 24VDC, 4A for 16 Transmitters.

  • Supply: 24VDC, 7A for 32  Transmitters.           

  • Cable

    • 1.5mm2 2 Core Shielded Cable for 24 VDC Power Supply.

    • 1.0mm2 2 Core Twisted Pair Cable for RS-485 Modbus RTU Communication.

Environmental

  • Storage Temp.: -20 to 60oc

  • Operating Temp.: -30 to 70oc

  • Humidity: Below 95% Non-Condensing

Weatherproof Housing

  • Protection Class: IP-65

  • Cabinet Material: Polycarbonate, Grey Colour.

  • Cable Entry: Thermoplastic (IP-68) for Weatherproof

  • Dimension: 305 mm (H) x 325 mm (W) x 170 mm (D)

  • Mounting: Wall Mounting / Stand Mounting

  • Weight: Approx 3.7 kg.

Output Signal (Optional)

Relay Output

  • 9 SPDT Relays of rating "10A/250VAC, 10A/30VDC".

  • 4 No. Relay for Warning & 4 No. for Trip & 1 no. for  Failsafe Operation for UNDER / OVER  OPEN condition of Transmitter.

  • Open Collector: Open Collector output with 100mA current capacity instead O/P of Relay.

  • RS-485 Port: Separate RS-485Modbus RTU Port for IntelliRepeater or PC Communication at a time

  • one Function is possible.

Error Monitoring

  • During Sensor Break / Open in the Transmitter connected to it, IntelliLogger shows SENSOR OPEN & Fail safe Relay activates.

  • During Over Range in the Transmitter connected to it, IntelliLogger shows OVER RANGE & Failsafe Relay activates.

  • During Under Range in the Transmitter connected to it, IntelliLogger shows UNDER RANGE & Failsafe Relay activates.

  • If communication fail occurs with any Transmitter  then IntelliLogger shows SLAVE NOT RESPONDING for that Transmitter.

Accessories (Optional)

  • FLP / WP Junction Box Enclosure for Inter Connection between Transmitters & IntelliLogger for easy maintenance.

  • IntelliRepeater Slave Monitor for Remote Display.

  • Hooter cum Flasher works on 24VDC or 230VAC.

  • LOG Manager PC Software to download data from IntelliLogger.

  • RS-485 to USB OR RS-232 convertor.

Flameproof Housing

  • Protection Class: IP-65 for Gas Gr.IIA & IIB, CMRI approved enclosure  & CCOE (optional).

  • Cabinet Material: Cast Aluminium alloy, LM-6

  • Cable Entry: 3/4" ET-Type for Flameproof

  • Dimension: 430 mm (H) x 410 mm (W) x 170 mm (D)

  • Mounting: Wall Mounting / Stand Mounting

  • Weight: Approx 13 kg.