AMBETRONICS ENGINEERS PVT. LTD.
IM-7711-WP-final

IM-7711-WP-final

Send Inquiry
IM-7711-FLP

Features
  • IntelliMaster is a 16/32 Channel Modbus ID Monitoring System for Transmitters are having RS-485 Modbus RTU Network Connectivity.
  • IntelliMaster has one more RS - 485 Modbus RTU Port for Remote Repeater Panel called as  IntelliRepeaterwhich will repeat all readings & Alarm conditions.
  • Multidrop RS - 485 Port eliminates separate cabling to each Transmitter and Monitor Panel.
  • Modbus - RTU Network can be connected in Ring Topology for Redendency.
  • Scan time for 16 Transmitter < 5 sec. & for 32 Transmitter < 10 sec.
  • Large 16 x 4 line Display with Configurable Backlit Option.
  • Auto Page Changing Facility available for easy viewing of Data, Relay & Fault Condition of each Transmitter.
  • Optional 8 Relays (SPDT) rated "10A / 250VAC, 10A / 30VDC" as Warning / Trip Relay with 1 no. Failsafe Relay which activates for UNDER / OVER / OPEN Condition of Transmitter.
  • Separate Alarm Setting for each Transmitter with Logic High / Low & Latching Facility.
  • Password Protected Menu with Password Changing Facility.
  • Easy Handling & Programming with 3 keys on Front Panel.
Applications
  • Clean Room Monitoring & Validation in Pharmaceutical, Laboratories, Bioscience
  • Room Mapping in Pharmaceutical
  • Pharmaceutical process validation with graph & scale report in Autoclave
  • Healthcare, Hospitals, Shopping Malls
  • Breweries, Steel Plants, Gas Turbines,
  • Leak detection, Solvent Vapors,
  • Personal Monitoring, Compressor Stations,
  • Emergency response, Equipment Maintenance
  • Pulp & Paper Industry, Fuel Loading Facilities
  • Waste Water Treatment Plants,
  • LNG / LPG Processing & Storage Facilities
  • Refineries & Petrochemical Plants Including Offshore
  • Drilling & Plant Shut-downs
  • ISO Certification Records, Validation process certifying,
  • Chemical & Hazardous area where data monitoring is essential
  • Food Processing
  • Cold Storage & Chilling Plant
  • Building Management & Energy Saving Systems
  • Meteorological, Weather Forecast Applications
  • Remote Indication location on tank taps as used in liquid level sensing &  control General
  • InputD: 16/32 Transmitters having RS-485 Modbus RTU Port.
  • Display
    • 16 x 4 Alphanumeric LCD with Configurable Backlit option.
    • 8 LEDs to indicate status of IntelliMaster.
    • 48 LEDs to indicate Alarm status of Transmitters in Group Function.
Control Action
  • 2 independent Alarm set points for each Transmitter with Latch & Non-Latch Facility.
  • User selectable Hysteresis & Logic Operation.
  • Setting: By using 3 keys on the front panel for WP & FLP models.
Performance

Scan Time
  • Less than 5 Sec. for 16 Transmitters having RS-485   Modbus RTU Port.
  • Less than 10 Sec. for 32 Transmitters having RS-485 Modbus RTU Port
Electrical
  • Supply Voltage: 190 to 270 VAC;   20%, 50Hz.
  • Power Rating: Approx 20W.
  • Transmitter: 24VDC, 4A for 16 Transmitters.
  • Supply: 24VDC, 7A for 32  Transmitters.            
  • Cable
    • 1.5mm2 2 Core Shielded Cable for 24 VDC Power Supply.
    • 1.0mm2 2 Core Twisted Pair Cable for RS-485 Modbus RTU Communication.
Environmental
  • Storage Temp.: -20 to 60oc
  • Operating Temp.: -30 to 70oc
  • Humidity: Below 95% Non-Condensing
Weatherproof Housing
  • Protection Class: IP-65
  • Cabinet Material: Polycarbonate, Grey Colour.
  • Cable Entry: Thermoplastic (IP-68) for Weatherproof
  • Dimension: 305 mm (H) x 325 mm (W) x 170 mm (D)
  • Mounting: Wall Mounting / Stand Mounting
  • Weight: Approx 3.7 kg.
Output Signal (Optional)

Relay Output
  • 9 SPDT Relays of rating "10A/250VAC, 10A/30VDC".
  • 4 No. Relay for Warning & 4 No. for Trip & 1 no. for  Failsafe Operation for UNDER / OVER / OPEN condition of Transmitter.
  • Open Collector: Open Collector output with 100mA current capacity instead O/P  of Relay.
  • RS-485 Port: Separate RS-485Modbus RTU Port for IntelliRepeater or PC Communication at a time one Function is possible.
Error Monitoring
  • During Sensor Break / Open in the Transmitter connected to it, IntelliMaster shows 'SENSOR OPEN' & Failsafe Relay activates.
  • During Over Range in the Transmitter connected to it, IntelliMaster shows 'OVER RANGE' & Failsafe Relay activates.
  • During Under Range in the Transmitter connected to it, IntelliMaster shows 'UNDER RANGE' & Failsafe Relay activates.
  • If communication fail occurs with any Transmitter  then IntelliMaster shows 'SLAVE NOT RESPONDING' for that Transmitter.
Accessories (Optional)
  • FLP / WP Junction Box Enclosure for Inter Connection between Transmitters & IntelliMaster for easy maintenance.
  • IntelliRepeater Slave Monitor for Remote Display.
  • Hooter cum Flasher works on 24VDC or 230VAC.
  • RS-485 to USB OR RS-232 convertor.
Flameproof Housing
  • Protection Class: IP-65 for Gas Gr.IIA & IIB, CMRI approved enclosure  & CCOE (optional).
  • Cabinet Material: Cast Aluminium alloy, LM-6
  • Cable Entry: 3/4" ET-Type for Flameproof
  • Dimension: 430 mm (H) x 410 mm (W) x 170 mm (D)
  • Mounting: Wall Mounting / Stand Mounting
  • Weight: Approx 13 kg.