Cookie Img

Multichannel Gas Monitor

Multichannel Gas Monitor
Multichannel Gas Monitor
Product Code : TC-800 Gas Monitor
Price And Quantity
Minimum Order Quantity :
1
Unit of Measure :
Piece/Pieces
Product Specifications
Material :
Poly-carbonate, Grey color For WP & Cast Aluminum alloy, LM-6 / C.I. Enclosure For FLP
Power Supply :
230V AC ±10%
Accuracy :
±0.5% of the full scale value mm
Display Type :
Digital Only
Range :
0 to 9999 programmable by user, reads % LEL , PPM or %V/V
Size :
305 mm (H) x 325 mm (W) x 170 mm (D) for WP & 350 mm (H) x 290 mm (W) x 170 mm (D) for FLP
Weight :
Approx. 2.5 (WP) & Approx 6.0 (FLP) Kilograms (kg)
Product Description

Features

  • User Friendly Operation by front keys
  • Scan Each Channel with Gas Concentration PPM, PPB, %V/V
  • Easy One Man Calibration at site
  • Open Loop Transmitter Sensor Break, open Indication
  • Individual Channel Skip, Hold Facility from Front Panel
  • Reading Offset Facility To Compensate The Field Error
  • High & Low Alarm Output with Programmable Latch & Non-Latch
  • Facility for common Relay & Relay Indication
  • Optional : Data Logging / Printer Interface / PC Software
  • Optional Relay Output for Each Channel
  • Suitable in Hazardous Area CCOE, PESO, CMRI & IP-65 approved.
Applications
  • Pulp & Paper Plants
  • Burner / Furnace Areas
  • Chemical & Petrochemical Plants
  • Heat Treatment Plants
  • Acid Alkalizes & Dyes Mfg. Plants
  • Paint Shop
  • Chemical Processing Plant
  • Sewage Plants
  • Offshore Drilling & Processing Platforms
  • Fertilizers Plants
  • Refineries
  • Power & Industrial Plants
  • Stack Monitoring
  • Gas Metering Stations
  • Chemical Storage Area
  • Bullet Yard / Storage Yards
  • Automotive Industries
  • Oil and Gas Industries
  • Hotel Industries
  • Coal Mine and Confined Areas
  • Gas Cylinder Bank
  • Gas Pipeline Projects
Technical Specifications

General Specification

Input

8 Channel, 4 to 20mA output from Oxygen / Toxic / Combustible Gas Transmitter of 2 wire/3wire

Range

0 to 9999 programmable by user, reads % LEL , PPM or %V/V

Resolution

0.01, 0.1, 1 programmable by users

Channel Capacity

Available 2Ch./4Ch./6Ch./8Ch.

LED Indication

8 No. RED LED for Alarm Indications of both set points AL1, AL2

Set Point

2 Independent set points individual for each channels with 2 common relay output

Control Action

LO/HI, HI/LO, LO/Very LO & HI-very HI, Programmable by user.

Setting

Setting by 5 keys on front panel  MODE, SHIFT INC,ENT PRN/ACK

Skip Channel

Individual Channel SKIP facility from front panel

Hold

Facility to HOLD the particular channel continuously

Scan Time

1 to 59 second programmable by users

Print Interval (Optional)

5 to 9999 sec. Print Interval for direct print out on 80 Column Dot Matrix Printer

 

Output Signal

Relay Output: 1 NO/C/NC relay contact rated 230VAC / 5A for Relay-1 (AL1) & Relay -2 (AL2)

Relay Latching: Programmable latch & Non-Latch facility for common relay & relay indication.

Optional:

a) Isolated RS-232/RS-485 Serial port with MODBUS RTU Protocol output

b) Parallel port for direct printout on 24/80/132 column printer without Computer with Data Logging facility

c) SMART LOG / SCADA SOFTWARE for online graph & data report for safety audit

d) Individual relay O/P can be given for each channel OR with grouping output

e) Flame Proof of Non Flame Proof Industrial Hooter, Hooter cum Flasher, Chart recorder, Cables, PC Software, Gas Transmitters, 24VDC power supply, Gas calibration kit.


 

Contact Us

17-B, Tarun Industrial Estate, Mogra Pada, New Nagardas Road, Andheri (East), Mumbai, Maharashtra, 400069, India
Phone :+917259672294