AMBETRONICS ENGINEERS PVT. LTD.
Programmable Flow Totalizer

Programmable Flow Totalizer

Send Inquiry

FTC 1000 PROGRAMMABLE FLOW TOTALIZER

FEATURES: 

  • Based on state of art latest micro controller technology with Watchdog feature for fail safe operation.
  • Acceptability of various analog inputs from Flow Transmitter.
  • A high resolution of 20000 counts (max) for Flow rate & 999999 counts (max) for Flow Totalizer & Batch Counter.
  • Highly informative, user friendly display & keyboard interface with separate indication for Flow rate, Total & Batch.
  • Relay control action can be programmable.
  • Programmable latch OR non-latch facility for relay & relay indication.
  • User selectable batch quantity, batch counter & reset facility through keyboard & external contacts. 
  • Non-Volatile battery backup memory to store data in case of power failure with configurable power up recovery option.
  • Isolated RS485 communication with MODBUS RTU Protocol
  • Isolated retransmission of process value signal (Optional).
  • Configurable retransmission range setting by users.

TECHNICAL SPECIFICATIONS:

Analog Input from  Flow Transmitter

1) Current 0-20mA / 4-20mA /0-1V Output from Flow Transmitter

Sensor Break

Under Range UndEr Over range our oPEn  indication for  4-20mA.

Range

0 to 19999 (5 digit) counts of Flow rate configurable as per Second, Min, Hour.
0 to 999999 (6 digit) counts of Flow Totalizer.
0 to 999999 (6 digit) Batch counter to know total no. of Batch completed.

Resolution

Field programmable decimal point selection for Ampere Indication by users.

Accuracy

Better than 0.1% of full scale reading..

Setting

By 6 keys on front panel.

Alarm Output

1 independent set point for Flow rate setting.

2 Independent set points for Totalizer setting

1 independent NO/C/NC contact for Flow rate indication.

2 independent NO/C/NC contact for Flow total indication.

1 independent NO/C/NC contact for fail safe operation.

Relay Specification

5Amp. / 250VAC, 5Amp. / 30VDC at resistive load. 

Control Action

L & H, H & VH, L & VL control action facility individual for each relay. 
Auto reset pulse output for Batch application 

Display

5 Digit for 20000 count for Flow rate indication.
6 Digit for 999999 count for Flow Totalizer indication.

8 L.E.D.s for RL1, RL2,  RL3, FAULT, PROG, SQR, TX, RX.

Square Root

Square root extraction facility.

Memory

Non-Volatile memory to store the Totalizer value, Batch count, in case of power failure with 4 options of power up recovery i.e. No memory recovery, Batch memory recovery, Totalizer memory recovery & All memory recovery.

Reset

Provision for Total reset from the panel as well as remote reset from back terminal through potential free contacts input for Totalizer.

Supply

230VAC +10% OR 110VAC +10% OR 24VDC.

Mounting

Panel mounting / Wall mounting for flameproof model.

Dimension

96(W) X 96(H) X 175(D) in mm. including backside connector.

Cutout

92(W) X 92(H) in mm.

Cabinet

ABS Plastic, White Color

Optional

a) Isolated RS485 Serial port with MODBUS RTU Protocol output for PC interface.
b) Isolated 4 to 20mA retransmission programmable output for recorder or PLC proportional to selective range.
c) Flameproof version is available on request for hazardous application. 

Important

MODBUS RTU Protocol support to update instrument setting through PC. Powerful SCADA software is available.

Weight

 Weight : 1.5 Kg.