- Piece/Pieces
- 1
- Piece/Pieces,
- 8000.00-
- Less than 3.6 Watts Watt (W)
- ±2% of Full Scale. mm
- Digital Only
Smart Gas Transmitter
- Provides a fast and reliable output by using Electro Chemical / Pellister Sensor Technology.
- Optimized for detection of smallest leak of Oxygen, -Toxic and Combustible Gases.
- Highly resistant to poisoning and etching.
- Capable of detecting down to PPM, %LEL & %V/V.
- Digital display of Gas Concentration on LED Display
- Standard 4-20mA signal output with configurable range.
- Easy handling and programming with 3 keys for Weatherproof Models.
- Non - Intrusive programming for Flameproof model using Magnetic pen.
- Password protected programming with password changing facility.
- One man Auto Software Gas Calibration.
- Optional Alarm relay contacts with two configurable Alarm levels & one Relay for fail safe relay.
- Optional STEL and TWA set points can be configured for Toxic Gases.
- Optional RS-485 communication port with MODBUS RTU Protocol.
Approval & Compliance for Flameproof : Certified to Ex-d IIA, IIB, T6, IP66
Standard Compliance :
- IS/IEC 60079-0 : 2004
- IS/IEC 60079-1 : 2007
- IS/IEC 60529 : 2001
Application
- Gas Metering skid
- Gas Cylinder Bank
- Oil & Gas Industries
- Gas Pipeline Project
- Refineries
- Cold Storage
- Sewage Plants
- Fertilizers Plants
- Stack Monitoring
- Chlorination Plant
- Ambient Monitoring
- Pulp & Paper Plants
- Gas Metering Station
- Burner / Furnace Areas
- Bullet Yard / Storage Yard
- Chemical Processing Plant
- Acid Alkalizes & Dyes Mfg. Plants
- Offshore Drilling & Processing Platforms
- Heat Treatment Plants
- Chemical Storage Area
- Control Atmosphere
- Power & Industrial Plants
- Coal Mine and Confined Area
- Chemical & Petrochemical Plants
- Automotive Industries / Paint Shops
TECHNICAL SPECIFICATIONS
General : | |
Detection Method | Electrochemical / Catalytic Bead Pellistor /Solid State |
Gases Detected | Oxygen / Toxic / Combustible / VOC (Please select from the table below). |
Display | 2-Line, 4-Digit 8 mm (H) Seven Segment LED Display 8 LEDs to indicate status of instrument |
Control Action | Two independent Alarm set points with Latch & Non-latch facility. |
User selectable Hysteresis and Logic option. | |
Configurable STEL and TWA set points for Toxic Gases (optional). | |
Setting | By using 3 Keys on front panel for Weatherproof Model By using Magnetic pen for Flameproof model |
Performance : | |
Accuracy | ±2% of Full Scale. |
Response Time | T20 < 18 Seconds |
T50 < 22 Seconds | |
T90 < 40 Seconds | |
Start-up Time | Less than 30 Seconds. |
Electrical : | |
Supply voltage | 18 to 36 VDC, Typically 24 VDC |
Power Consumption | Less than 3.6 watt |
Cable | 3 wire (1.5mm2) Flexible or armoured shielded cable |
Weatherproof Housing : | |
Protection Class | IP-65 |
Cabinet Material | Polycarbonate, grey colour |
Cable Entry | Thermoplastic cable gland (IP 68) |
Dimension | 155mm (H) x 100 mm (W) x 55 mm (D) - (1 Glands) |
| 155mm (H) x 120 mm (W) x 55 mm (D) - (2 Glands) |
Mounting | Wall Mounting / Stand Mounting / Pipe Mounting |
Weight | Approx 500 Grams |
Output Signal : | |
Standard | 4-20mA Current Output with configurable range selection. |
Optional | Three SPDT Relays (one for FailSafe and Two for Alarm indication) of rating 2A/120VAC, 2A/24VDC. |
Optional | RS-485 Communication port with MODBUS RTU protocol. |
Error monitoring | |
Operating Temperature | -15ºC +to 50ºC |
Storage temperature | -10ºC to +60ºC |
Humidity | Less than 95% non-condensing |
Accessories (Optional) :
- CE certified 24 VDC Power supply.
- Canopy & Mounting stand.
- Gas Calibration Kit (0.5,1, 3,10)Liter.
- Hooter Cum Flasher.
- Remote Control for programming.
- Gas Sampling & Conditioning System.
- RS-485 to USB OR RS-232 convertor
- PC Based SCADA Software, Modem
Flame proof Housing
Protection Class | IP-66 for Gas GI. HA, IIB & IIC, CMRI (CIMFR) approved Enclosure, CCOE (Optional). |
Cabinet Material | Cast Aluminium alloy, LM-6 |
Cable Entry | Double compression cable gland (Ex-Proof), 3AWET-type |
Dimension | 175mm (H) x 205mm (W) x 120 mm (D) - (1 Glands) 175mm(H) x 250 mm(W) x 120 mm (D) - (2 Glands) |
Mounting | Wall Mounting / Stand Mounting / Pipe Mounting |
Weight | Approx 2.0 Kg |
- 300 Per Day
- 1 Week
- All India
- Certified to EX-d IIA, IIB, T6, IP66
17-B, Tarun Industrial Estate, Mogra Pada, New Nagardas Road, Andheri (East) Mumbai Maharashtra India +918037301604
Phone :+918037301604